The numbers you actually
use on the job.
Charging targets, what the split is telling you, A2L handling, and the two electrical checks that settle a no-cool call. Print the card, laminate it, put it on the visor.
Download the cardWhich method goes with which metering device
Charge to the metric the device actually controls. The nameplate wins over anything on this page.
Read it off the right column
The two definitions people mix up on a hot job site, written out in full.
Air
Airflow first. A charge chased on a system starved for air is a charge you'll be chasing again next week.
350 to 425
at 75°F, 50% RH
above 50%
What the split is telling you
One number you already have on the gauge, and what it means, without calling anybody.
14°F
24°F
The math
Three formulas that cover most of what gets worked out in a truck.
R-454B, what is actually different
It's an A2L blend. Four handling rules and three numbers worth knowing.
- Pull liquid from the cylinder. It's a blend, so drawing vapour changes the mix.
- Cylinder threads are left hand, double ring on the knurl. System side stays right hand.
- A2L rated tools and recovery tank. No ignition sources anywhere near the work.
- New equipment only. Never a retrofit, never mixed with another refrigerant.
class
R-410A
Electrical
The two checks that settle a no-cool call fastest.
Evacuation
The step that gets skipped, and the one that actually proves the job.
Ranges from ACCA Manual T and manufacturer service data. A2L class per ASHRAE 34, leak detection per UL 60335-2-40, unbalance per NEMA MG-1, evacuation per ANSI/ACCA 5 QI. The nameplate and the maker's chart always win.